| STANDARDS OF PRACTICE
|
| |
| 1.INTRODUCTION |
| |
|
1.1 The Florida Association of Building
inspectors (FABI) is a not-for-profit professional society established in
1984. Membership in FABI is voluntary and its members include private, fee-paid
home inspectors. FABI’s objectives include promotion of excellence within the
profession and continual improvement of its members’ inspection services to the
public.
|
| |
| 2.PURPOSE AND SCOPE |
| |
2.1 A. The purpose of these Standards of Practice is to
establish a minimum and uniform standard for private, fee-paid home inspectors
who are members of the Florida Association of Building Inspectors. Home
Inspections performed to these Standards of Practice are intended to provide
the client with information regarding the condition of the systems and
components of the home as inspected at the time of the Home Inspection.
B. These standards shall not be construed as limiting the scope of the
inspection process in those areas where the inspector is qualified and/or has
special knowledge.
|
|
2.2 The inspector shall:
A. Inspect:
1. Readily accessible systems and components of homes listed in these Standards
of Practice.
2. Installed systems and components of homes listed in these Standards of
Practice.
B. Describe:
Systems and components by their nomenclature, capacity, output
rating or other means of descriptive terminology typically used by tradesmen.
C. Report:
1. On those systems and components inspected which, in the professional opinion
of the inspector, are not functioning properly, are unsafe, are significantly
deficient or are near the end of their service lives.
2. A reason why, if not self-evident, the system or component is significantly
deficient or near the end of its service life.
3. The inspector’s recommendations to correct or monitor the reported
deficiency, i.e. needs repair, needs additional evaluation, etc.
4. On any systems and components designated for inspection in these Standards
of Practice which were present at the time of the Home Inspection but were not
inspected and a reason why they were not inspected.
|
|
2.3 These Standards of Practice are not intended to limit inspectors from:
A. Including other inspection services, systems or components in addition to
those required by these Standards of Practice.
B. Specifying repairs, provided the inspector is appropriately qualified and
willing to do so.
C. Excluding systems and components from the inspection if requested by the
client.
|
| |
| STRUCTURE (Including interior and exterior sections)
|
| |
3.1 The inspector shall:
TOP
A. Inspect:
1. Tthe structural components including visible portions of the foundation,
walls, posts, beams, columns, joists, trusses, and framing.
2. By probing of structural components where deterioration is
suspected or where clear indications of possible deterioration exist. Probing
is NOT required when, in the opinion of the inspector, probing would only
further damage any area already identified as defective or where no
deterioration is visible.
3. The exterior grade and drainage including water runoff
management components such as gutters and downspouts.
4. The vegetation, grading, surface drainage, and the
retaining walls on the property when any of these are likely to adversely
affect the building.
5. The interior doors and windows, and their operating
mechanisms, locks and latches.
6. The exterior wall cladding, flashing and trim.
7. All exterior doors
8. Attached decks, balconies, stoops, steps, porches, and
their associated railings.
9. Walkways, patios, and driveways leading to the dwelling
entrances.
10. Interior walls, ceilings, and floors.
11. Steps, stairways, and railings.
12. Countertops and installed cabinets.
13. Garage doors and garage door operators.
14. The insulation and vapor retarders in unfinished spaces.
15. The ventilation of attics and foundation areas.
16. The mechanical ventilation systems.
B. Describe:
1. The foundation and report the methods used to inspect the
under-floor crawl space, if present.
2. The methods used to inspect the attic space, if present.
Entry into and traversing of the under-floor crawl space and the attic are at
the discretion of the inspector
3. The floor structure.
4. The wall structure.
5. The ceiling structure.
6. The roof structure and report the methods used to inspect
the attic.
7. The insulation in unfinished spaces.
C. Report:
1. Evidence of failed of structural components
2. Deterioration of structural components
3. The absence of insulation in unfinished spaces at
conditioned surfaces.
4. Windows with broken or cracked glass, obvious signs of
failed seals in dual paned windows, inoperable locks or latches or defective
balance springs or operating mechanisms.
5. Conditions that require professional engineering services
or additional professional engineer evaluation to determine structural adequacy
of a component.
|
3.2 The inspector is NOT required to:
A. Enter or traverse any under-floor crawl space or attic, if in the opinion of
the inspector:
1. An unsafe or unsanitary condition exists .
2. Inadequate clearance exists to allow entering or traversing.
3. The potential exists to cause damage to ductwork or stored items.
B. Open or operate any windows or doors that are permanently or temporarily
secured by mechanical means, are painted shut, or are blocked by stored items.
C. Provide any engineering service or architectural service.
D. Offer an opinion as to the adequacy of any structural system or component.
E. Inspect:
1. Temporary screening, shutters, awnings, and similar seasonal accessories.
2. Fences.
3. Geological, geotechnical or hydrological conditions.
4. Recreational facilities.
5. Outbuildings.
6. Seawalls, break-walls, and docks.
7. Erosion control and earth stabilization measures.
8. The paint, wallpaper, window treatments, and other finish treatments.
|
| |
| 4.ROOF SYSTEMS
|
| |
|
4.1 The inspector shall:
A. Inspect: (by entering onto and traversing the roof surface if
appropriate)
1. The roofing material
2. The soffits and fascia.
3. The flashings.
4. The skylights, chimneys, and roof penetrations.
B. Describe:
1. The roofing material and type
2. The style of the roof (i.e. gable, hip, mansard, low slope)
C. Report :
1. The methods used to
inspect the roof
2. Roofing material failures or damage to the roofing material
3. Visible signs of leaking in ceilings, walls, roof
sheathing, trusses, rafters, joists, soffits and fascia.
4. Unworkmanlike or unconventional repairs and materials
|
4.2 The inspector is NOT required to:
A. Inspect:
1. Antenna or other installed accessories
2. Interiors of flues or chimneys which are not readily accessible.
B. Enter onto or traverse the roof surface when, in the opinion of the
inspector, the following conditions exist:
1. Te roof slope is excessive to safely enter or traverse
2. There is no safe access to the roof
3. The climatic conditions render the roof unsafe to enter or traverse
4. The condition of the roofing material or roof decking render the roof unsafe
to enter or traverse
|
| |
| 5.PLUMBING SYSTEM
TOP
|
| |
|
5.1 The inspector shall:
A. Inspect:
1. The interior water supply and distribution systems including all fixtures,
faucets, and components not encased in floors, walls, and ceilings, or
otherwise hidden from view.
2. The drain, waste and vent systems.
3. The water heating equipment.
4. Shower stalls
5. The vent systems, flues, and chimneys.
6. The drainage sumps, sump pumps, and related piping.
7. The irrigation
system.
B. Describe:
1. The water supply, drain, waste, and vent piping materials.
2. The water heating equipment including the energy source.
3. The location of main water and main fuel shut-off valves.
4. The type of irrigation system (well, municipal source, reclaimed water, etc.
C. Report:
1. Leaks in supply lines, fixtures, and faucets.
2. Leaks in shower stalls.
3. Low water pressure to one or more fixtures.
4. Leaking or defective water heaters.
5. Non functional or clogged drains.
6. On the presence of polybutylene supply lines or cast iron waste lines.
7. Defective or ineffective pumps and irrigation system component parts
(exclusive of wells).
|
5.2 The inspector is NOT required to:
A. Inspect:
1. Wells, or water storage related equipment.
2. Water conditioning systems.
3. Solar water heating systems.
4. Fire sprinkler systems.
5. Private waste disposal systems.
B. Determine:
1. Whether water supply and waste disposal systems are public or private.
2. The quantity or quality of the water supply, including the quantity or
quality of the irrigation system supply.
C. Operate safety valves or shut-off valves.
|
| |
| 6.ELECTRICAL SYSTEM
|
| |
6.1 The inspector shall:
1. The service entry.
2. The service entrance conductors, cables, and raceways.
3. The service equipment and main disconnects.
4. The service grounding.
5. The interior components of service panels and sub panels.
6. The conductors.
7. The overcurrent protection devices.
8. All accessible installed lighting fixtures, switches, and receptacles.
9. The ground fault circuit interrupters.
10. The arc fault circuit interuptors
B. Describe:
1. The amperage and voltage rating of the service.
2. The location of main disconnect(s) and sub panels.
3. The wiring method or type.
C. Report:
1. On the presence of solid conductor aluminum branch circuit wiring.
2. On the presence of electric
panels with a documented history of functional
defects
3. On the presence of obsolete wiring or components, i. e. knob and tube
wiring, fused overprotection devices, two prong wall outlets, etc.
4. On the presence of unrated electrical components.
5. On the presence of undersized wiring, inappropriate double tapping / double
lugging, improperly routed, protected, or terminated wiring.
6. On the presence of evidence of overheating in electrical components
7. On the lack of, or improper grounding
8. On the absence of smoke detectors.
|
6.2 The inspector is NOT required to:
A. Inspect:
1. Remote control devices unless the device is the only control device.
2. Security alarm systems and components.
3. Low voltage wiring, systems and components, ancillary wiring and systems and
components not a part of the primary electrical power distribution system.
B. Measure amperage, voltage or impedance.
|
|
| 7.HEATING SYSTEM
TOP |
| |
7.1 The inspector shall:
A. Inspect:
1. The installed heating equipment.
2. The fuel storage and fuel distribution systems.
3. The vent systems, flues, and chimneys.
B. Describe:
1. The energy source.
2. The heating method by its distinguishing characteristics.
3. The heating system capacity in BTUs or kilowatts
C. Report:
1. The location and condition of the air handler unit / furnace
2. The operation of the thermostat
3. The location, type, and condition of the ductwork
4. Improperly vented combustion vents or the potential for backdrafting in
combustion vented systems.
5. The heat rise obtained during operation
6. Systems that are inoperable or fail to operate in the manner which was
intended
7. Conditions that will result in reduced component life expectancy, pre-mature
failure, or inefficient system operation.
|
7.2 The inspector is NOT required to:
A. To inspect:
1. Interiors of flues or chimneys which are not readily accessible
2. Heat exchangers.
3. Humidifiers or dehumidifiers.
4. Electronic air filters.
5. Solar space heating systems.
B. Determine heat supply adequacy or distribution balance.
C. Operate heat pump systems when ambient temperatures pose the potential for
damage to the heating system.
|
| |
| 8.AIR CONDITIONING SYSTEMS |
| |
8.1 The inspector shall:
A. Inspect the installed central and through-wall cooling
equipment.
B. Describe:
1. The energy source.
2. The cooling method by its distinguishing characteristics.
C. Report:
1. The condition of the condensing unit
2. The condition of the evaporator coil (when accessible)
3. The operation of the thermostat
4. The type and condition of the ductwork
5. The temperature differential achieved by the system
6. Systems that are inoperable or fail to operate in the manner which was
intended
7. Conditions that will result in reduced component life expectancy, pre-mature
failure, or inefficient system operation.
|
8.2 The inspector is NOT required to:
A. Inspect:
1. Electronic air filters.
2. Humidistats
B. Determine cooling supply adequacy or distribution balance.
C. Determine indoor air quality.
D. Operate the air conditioning system when ambient temperatures pose the
potential for damage to the air conditioning system.
|
|
| 9.FIREPLACES AND SOLID FUEL BURNING APPLIANCES |
| |
9.1 The inspector shall:
A. Inspect:
1. The system components.
2. The vent systems, flues, and chimneys.
B. Describe:
1. The fireplaces and solid fuel burning appliances.
2. The chimneys.
C. Report:
1. The type of fireplace (masonry, insert, free standing, etc.)
2. The condition of the fire brick or refractory panels, flue door, chimney /
chimney chase cap, and flue cap.
3. Unsafe conditions
|
9.2 The inspector is NOT required to:
A. Inspect:
1. The interiors of flues or chimneys.
2. The firescreens and doors, if not permanently attached.
3. The seals and gaskets.
4. The automatic fuel feed devices.
5. The mantles and fireplace surrounds.
6. The combustion make-up air devices.
7. The heat distribution assists whether gravity controlled or fan assisted.
B. Ignite or extinguish fires.
C. Determine draft characteristics.
D. Move fireplace inserts or stoves or firebox contents.
|
|
| 10.GENERAL LIMITATIONS AND
EXCLUSIONS TOP |
| |
10.1 General limitations:
A. Inspections performed in accordance with these Standards of
Practice
1. Are not technically exhaustive.
2. Will not identify concealed conditions or latent defects.
B. These Standards of Practice are applicable to buildings with four or fewer
dwelling units and their garages or carports.
|
10.2 General exclusions:
A. The inspector is not required to perform any action or make
any determination unless specifically stated in these Standards of Practice,
except as may be required by lawful authority.
B. Inspectors are NOT required to determine:
1. The condition of systems or components which are not readily accessible.
2. The remaining life of any system or component.
3. The strength, adequacy, effectiveness, or efficiency of any system or
component.
4. The causes of any condition or deficiency.
5. The methods, materials, or costs of corrections.
6. Future conditions including, but not limited to, failure of systems and
components.
7. The suitability of the property for any specialized use.
8. Compliance with regulatory requirements (codes, regulations, laws,
ordinances, etc.)
9. The market value of the property or its marketability.
10.The advisability of the purchase of the property.
11. The presence of potentially hazardous plants or animals including, but not
limited to wood destroying organisms or diseases harmful to humans.
12. The presence of any environmental hazards including, but not limited to
molds, toxins, carcinogens, noise, and contaminants in soil, water, and air.
13. The effectiveness of any system installed or methods utilized to control or
remove suspected hazardous substances.
14. The operating costs of systems or components.
15. The acoustical properties of any system or component.
C. Inspectors are NOT required to offer:
1. Or perform any act or service contrary to law.
2. Or perform engineering services.
3. Or perform work in any trade or any professional service other than home
inspection.
4. Warranties or guarantees of any kind.
D. Inspectors are NOT required to operate:
1. Any system or component which is shut down or otherwise inoperable
2. Any system or component which does not respond to normal operating controls.
3. Shut-off valves.
E. Inspectors are NOT required to enter:
1. Any area which will, in the opinion of the inspector, likely be dangerous to
the inspector or other persons or damage the property or its systems or
components. 2. the under-floor crawl space or attics which are not readily
accessible.
F. Inspectors are NOT required to inspect:
1. Underground items including, but not limited to underground storage tanks or
other underground indications of their presence, whether abandoned or active.
2. systems or components which are not installed.
3. Decorative items.
4. Systems or components located in areas that are not entered in accordance
with these Standards of Practice.
5. Detached structures other than garages and carports.
6. Common elements or common areas in multiunit housing, such as condominium
properties or cooperative housing.
G. Inspectors are NOT required to:
1. Perform any procedure or operation which will, in the opinion of the
inspector, likely to be dangerous to the inspector or other persons or damage
the property or its systems or components.
2. Move suspended ceiling tiles, personal property, furniture, equipment,
plants, soil, snow, ice, or debris.
3. Dismantle any system or component, except as explicitly required by these
Standards of Practice
|
|
| 11.HOUSEHOLD APPLIANCES (optional) |
| |
11.1 The inspector and the client
may agree to the inspection of optional items. When this agreement is made the
following standards shall apply: (Household appliances to be inspected are
limited to the following - Built-in central vacuums, ranges, cook-tops,
built-in dishwashers, food waste disposers, garage door openers, built-in
ovens, built-in microwave ovens, refrigerators, freezers, clothes washers,
clothes dryers, built-in trash compactors, ceiling fans or whole-house fans.)
|
11.2 The inspector shall:
A. Inspect:
1. Household appliances specifically identified to be examined during the
inspection.
2. The basic operation of appliances included in the inspection, limited to
those items listed above.
B. Describe:
1. The type of appliance and its general function
C. Report:
1. The completion of a full cycle of the appliances intended use
2. The adequacy of controls or switches in operating the appliance
3. Missing or defective components or parts
4. Failure or stoppage during operation.
5. The presence or absence of necessary safety devices
6. The success or failure of the appliance to perform in the manner intended.
|
11.2 The inspector is NOT required to:
A. Activate any system or appliance that is shut down,
disconnected, or otherwise rendered inoperable.
B. Operate or evaluate any system, component or appliance that does not respond
to normal user controls
C. Operate any gas appliance that requires the manual lighting of a pilot light
or burner device.
D. Operate any system or appliance that requires the use of special codes,
keys, combinations, or devices.
E. Operate any system, component, or appliance where in the
opinion of the inspector, damage may occur.
F. Determine oven or cook top thermostat(s) calibration, adequacy of heating
elements, operate or evaluate self cleaning oven cycles, indicator lights,
timers, clocks or timed features, defrost cycles or frost free features of
refrigerators and freezers.
G. Determine leakage from microwaves ovens.
H. Determine the presence or operation of back draft damper devices in exhaust
devices.
I. Examine any wine cooler, sauna, steam-room, still or other water producing
or purification device, kiln, toaster, ice maker, coffee-maker, can-opener,
bread warmer, blender, instant hot water dispenser, or any other similar small,
ancillary or non- built- in appliances, including commercial grade kitchen
appliances.
|
|
12.POOLS AND SPAS (optional)
TOP
|
12.1 The inspector and the client may agree to the inspection of optional
items. When this agreement is made the following standards shall apply:
|
12.2 The inspector shall:
A. Inspect:
1. Pools, spas, and normally necessary and present equipment such as: pumps,
heaters, filters, lights, ladders, railings related mechanical and electrical
connections, and safety items such as barriers
2. Enclosures, fencing, barriers, and related gates.
3. Decks, patios, and adjoining structures and drainage related to the
inspected pool or spa.
B. Describe:
1. Type of pool or spa examined (Concrete, Vinyl lined, Fiberglass, Above
ground, etc).
2. Conditions limiting or otherwise inhibiting inspection, such as water
clarity
3. Condition of visible portions of systems, structures, or components
C. Report:
1. Pool and spa finish condition, including pool shell cracks
2. Cracked, broken, or missing water line tiles
3. efective or unsafe pumps, heaters, filter housings, main drain covers, and
related mechanical and electrical connections.
4. Missing or damaged safety barrier components around the pool.
5. Excessive settlement of the pool deck
6. Inadequate drainage of the pool deck.
|
12.3.The inspector is NOT required to:
A. Enter the pool or otherwise come into contact with pool or spa water to
examine the system, structure or components.
B. Determine adequacy of pool or spa jet water force or bubble effect.
C. Determine structural integrity of the pool or determine or identify leakage
of any kind.
D. Evaluate thermostat(s) or their calibration, heating elements, chemical
dispensers, water chemistry or conditioning devices, chlorine generators, low
voltage or computer controls, remote controls, timers, filter medium, sweeps or
cleaners, pool or spa covers and related components.
E. Operate or evaluate filter backwash systems.
F. Turn on gas supplies or light pilot lights necessary for the operation of
gas fired pool or spa heaters.
G. Examine accessories, such as, but not limited to: Solar heating systems,
aerators or air motors / blowers, fiber optic lighting, diving or jump boards,
skimmers, waterfalls, slides or steps.
|
|
13.DOCKS AND SEAWALLS (optional)
|
13.1 The inspector and the client may agree to the inspection of optional
items. When this agreement is made the following standards shall apply.
|
13.2 The inspector shall:
A. Inspect:
1. The seawall components, including but not limited to, the seawall cap,
bulkhead, panels, footings, and any other component which is visible from the
land side of the structure. (In-water inspection by walking on the bottom or
diving is optional and is not considered a mandatory part of a seawall
inspection).
2. The land side components of the wall system for signs of
settlement or soil loss by either visual means or probing the soil behind the
seawall, or a combination of both.
3. The dock structure, including but not limited to pilings, collars,
stringers, joists, and decking.
4. Boat house walls and roof, if present. (Standards of Practice for Roof
Systems apply)
5. Operation of mechanical boat lifts and davits.
6. Visible components of water and electric service, if present. (Standards of
Practice for Electrical Systems and Plumbing Systems apply)
B. Describe:
1. The method of marine construction and the materials used, to include type of
seawall, bulkhead or panel material, visible reinforcements pilings, decks,
etc.
C. Report:
1. The evidence of structural deterioration, failure, or inadequacy in the
seawall and dock components.
2. Settlement or soil loss behind the seawall
3. Fastener failures in dock and deck components
4. Mechanical failures of boat lifts and davits
|
13.3 The inspector is NOT required to:
A. Dig or otherwise unearth tie-backs, anchors, retaining
walls or other seawall or dock components below landside or waterside grade.
B. Determine the load capacity of boat lifts
C. Offer an opinion as to the structural adequacy, life expectancy, or
expansion potential of any seawall or dock
D. Inspect adjoining or contiguous seawall systems or storm sewers projecting
through the bulkhead.
|
|
| 14. Glossary of Terms |
| |
| Alarm Systems:
TOP
|
| |
|
Warning devices, installed or free standing, including but not
limited to: carbon monoxide detectors, flue gas and other spillage detectors,
security equipment, ejector pumps and smoke alarms.
|
| |
| Architectural Service:
|
|
Any practice involving the art and science of building design
for construction of any structure or groupings of structures and the use of
space within and surrounding the structures or the design for construction,
including but not specifically limited to, schematic design, design
development, preparation of construction contract documents, and administration
of the construction contract.
|
| |
| Automatic Safety Controls: |
|
Devices designed and installed to protect systems and
components from unsafe conditions.
|
| |
| Component: |
|
A part of a system.
|
| |
| Decorative: |
|
Ornamental; not required for the operation of the essential
systems and components of a home.
|
| |
| Describe: |
|
To report a system or component by its type or other observed,
significant characteristics to distinguish it from other systems or components.
|
| |
| Dismantle: |
|
To take apart or remove any component, device or piece of
equipment that would not be taken apart or removed by a homeowner in the course
of normal and routine homeowner maintenance.
|
| |
| Engineering Service: |
|
Any professional service or creative work requiring
engineering education, training and experience and the application of special
knowledge of the mathematical, physical and engineering services to such
professional service or creative work as consultation, investigation,
evaluation, planning, design and supervision of construction for the purpose of
assuring compliance with the specifications and design, in conjunction with
structures, buildings, machines, equipment, works or processes.
|
| |
| Further Evaluation: |
|
Examination and analysis by a qualified professional tradesman
or service technician beyond that provided by the home inspection.
|
| |
| Home Inspection: |
|
The process by which an inspector visually examines the
readily accessible systems and components of a home which describes those
systems and components in accordance with these Standards of Practice.
|
| |
| Household Appliances: |
|
Kitchen, laundry, and similar appliances, whether installed or
free-standing.
|
| |
| Inspect: |
|
To examine readily accessible systems and components of a
building in accordance with these Standards of Practice, using normal operating
controls and opening readily openable access panels
|
| |
| Inspector: |
|
A person hired to examine any system or component of a
building in accordance with these Standards of Practice.
|
| |
| Installed: |
|
Attached such that removal requires tools.
|
| |
| Normal Operating Controls: |
|
Devices such as thermostats, switches or valves intended to be
operated by the homeowner.
|
| |
| Readily Accessible: |
|
Available for visual inspection without requiring moving of
personal property, dismantling, destructive measures, or any action which will
likely involve risk to persons or property.
|
| |
| Readily Openable Access Panel: |
|
A panel provided for homeowner inspection and maintenance that
is within normal reach, can be removed by one person and is not sealed in
place.
|
| |
| Recreational Facilities: |
|
Spas, saunas, steam baths, swimming pools, exercise,
entertainment, athletic, playground or other similar equipment and associated
accessories.
|
| |
| Report: |
|
To communicate in writing.
|
| |
| Representative Number: |
|
One component per room for multiple similar interior
components such as window and electric outlets; one component on each side of
the building for multiple similar exterior components.
|
| |
| Roof Drainage Systems: |
|
Components used to carry water off a roof and away from a
building.
|
| |
| Significantly Deficient: |
|
Unsafe or not functioning.
|
| |
| Shut Down: |
|
A state in which a system or component cannot be operated by
normal operating controls.
|
| |
| Solid Fuel Burning Appliances: |
|
A hearth and fire chamber or similar prepared place in which a
fire may be built and which is built in conjunction with a chimney; or a listed
assembly of a fire chamber, its chimney and related factory-made parts designed
for unit assembly without requiring field construction.
|
| |
| Structural Component: |
|
A component that supports non-variable forces or weights (dead
loads) and variable forces or weights (live loads).
|
| |
| System: |
|
A combination of interacting or interdependent components,
assembled to carry out one or more functions.
|
| |
| Technically Exhaustive: |
|
An investigation that involves dismantling; the extensive use
of advanced techniques, measurements, instruments, testing, calculations, or
other means.
|
| |
| Under-floor Crawl Space: |
|
The area within the confines of the foundation and between the
ground and the underside of the floor.
|
| |
| Unsafe: |
|
A condition in a readily accessible, installed system or
component which is judged to be a significant risk of personal injury during
normal, day-to-day use.The risk may be due to damage, deterioration, improper
installation or a change in accepted residential construction standards.
|
| |
| Wiring Methods: |
|
Identification of electrical conductors or wires by their
general type, such as “non-metallic sheathed cable” (“Romex”), “armored cable”
(“bx”) or “knob and tube”, etc.
|
| |
| |
Standards of Practice. Effective September 1, 2007.
© Copyright 2007 Florida Association of Building Inspectors, Inc.
|
| |
|
|
|
|